Belimo搏力谋电动球阀蝶阀:
Belimo搏力谋已成为暖通空调领域的者,产品包括belimo风门执行器、风阀执行器、belimo电动蝶阀、belimo电动调节阀、belimo电动球阀、belimo电动两通阀。
belimo搏力谋控制球阀的技术:特殊的流量配置装置—配流盘
搏力谋belimo解决球阀的控制稳定性问题。搏力谋控制球阀在的特殊装置---配流盘。配流盘是一侧为凹型的球面,与球型阀芯表面良好配合。流量通过球型阀芯的配流盘V型开口之间的开度得到精密控制。因而将球阀C值减小到相同规格座阀的C值。配流盘确定了阀门的特性。备有不同形状开口的配流盘,因而每种规格的阀门可以有不同的C值。
作为一家始创于1975年6月1日的瑞士公司,Belimo已经从一家小型公司成长为现在的上市公司,不仅在世界各地设立了分公司及办公网点,并成为了暖通空调领域的者。在过去的30年里,Belimo的品牌,产品得到了众多客户及终端用户的一致认可;Belimo象征着的产品,快速的供货和永无止境的创新。为了继续加大Belimo的成功步伐,Belimo亚太将全力以赴的为广大客户提供应用在加热,通风及空调等领域的*品质的风门和控制阀。
Belimo搏力谋电动球阀蝶阀技术参数:
Open/close ball valve, 2-way, Internal thread
• For open and closed cold and warm water systems
• For shut-off functions on the water side and 2-point
controls in air handling units and heating systems
• Air bubble tight
Type kvs
[ m³/h]
DN
[ ]
Rp
[”]
PN
[ ]
R2015-S1 15 15 1/2 40
R2020-S1 15 20 3/4 40
R2020-S2 32 20 3/4 40
R2025-S2 26 25 1 40
R2032-S2 32 32 1 1/4 25
R2040-S2 31 40 1 1/2 25
R2050-S3 49 50 2 25
Functional data Media Cold and warm water, water with glycol up to
max. 50% vol.
Medium temperature -10...120°C
Medium temperature note The allowed media temperature can be limited,
depending on the type of actuator. Limitations
can be found in the respective data sheets of
the actuators.
Closing pressure ?ps 1400 kPa
Differential pressure ?pmax 1000 kPa
Differential pressure note 200 kPa for low-noise operation
Leakage rate Leakage rate A, air-bubble-tight (EN 12266-1)
Pipe connectors Internal thread according to ISO 7-1
Angle of rotation 90°
Installation position Upright to horizontal (in relation to the stem)
Maintenance Maintenance-free
Materials Housing Brass body nickel-plated
Closing element Stainless steel
Stem Stainless steel
Stem seal O-ring EPDM
Valve seat PTFE, O-ring EPDM
!
• The valve has been designed for use in stationary heating, ventilation and air-conditioning
systems and is not allowed to be used outside the specified field of application, especially
in aircraft or in any other airborne means of transport.
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied during installation.
• The valve does not contain any parts that can be replaced or repaired by the user.
• The valve may not be disposed of as household refuse. All locally valid regulations and
requirements must be observed.
• When determining the flow rate characteristic of controlled devices, the recognised
directives must be observed.
R2..-S..